such a device is not available to you, a diligent individual can get similar results by manually
graphing the temperature displayed on the control every 15 minutes.
The following charts are all taken from a single installed system. They demonstrate the charting
process and show the results of incorrect settings. The temperatures on the chart begin at the
moment the compressor is turned off and cover a complete thaw and re-freeze cycle in 15
minute increments.. Remember, the actual temperatures are not as important as is the shape of
the curve.
Chart # 1 -
The “Ideal” Chart.
“A”- Compressor OFF - temperature of
frozen eutectic solution rises.
“B” - Eutectic point reached - thaw
starts.
“C” - Thaw continues - surface
temperature rises.
“D” - Eutectic thawed - temperature
rise rate increases.
“E” - Compressor turns on - plate
surface temperature rapidly drops
(little to no eutectic freezing occurs).
“F” - Compressor continues to run - eutectic solution begins to freeze and the rate of temperature
change slows down.
“G” - Compressor turns off.
“H” - Surface temperature rapidly rises back to the solution eutectic point.